SLUAB09 October 2025 AMC0386-Q1 , TPS61170 , TPS61170-Q1 , TPSI2140-Q1
As electric vehicles evolve to deliver extended range and enhanced power capabilities, battery systems are increasingly adopting architectures of 800V or higher. User safety remains paramount in these high-voltage (HV) systems. Consequently, all HV components must maintain isolation from protective earth through high-resistance pathways. Insulation failures can arise from various causes; including wire harness deterioration, aging of power-handling components, or extreme electrical stress events, such as damage to Y-capacitors. The system enters an unsafe condition when any single insulation failure occurs. Electrical shock is not necessarily caused by an initial reduction in impedance directly, however, a reduction requires immediate warning as the condition presents a potential life-threatening risk if human contact occurs.
Isolated power systems, including DC fast-charging stations, must adhere to the applicable safety standards. These standards vary by region, as illustrated in Table 1-1.
| Region | Standard | Scope |
|---|---|---|
| Europe | IEC 61851-23 | Defines the vehicle?side-monitor function that the OBC must support when communicating with a DC fast charger. |
| Europe | IEC?61557?8 | General requirements for IMDs used in information technology systems, which are adopted for automotive OBCs |
| Europe | ISO?6469?3 | Vehicle?wide safety requirements, referenced by ECE?R100. |
| North America | UL?2231?1 | UL?2231?2 | Specifies vehicle?side protection functions that must work with the IMD of the charger. |
| China | GB/T?18487.1 | Chinese counterpart of IEC?61851?21 and IEC 61851?23. |
| China | GB/T 18487.4 | Part 4 is the discharging requirements for electric vehicles. |
| Japan | JARI | JSAE Guidelines | Aligns with ISO?6469?3 and IEC?61557?8, adding Japanese environmental limits. |
| Other Regions (Australia (AS), New Zealand (NZ), Korea, India, and so forth) | National adoptions of IEC?61851?23, IEC?61557?8, and ISO?6469?3 | Same functional scope as the European version with minor climate or labeling variations. For example, AS/NZS?61851?21?1, KS?C?IEC?61851?21?1, BIS?ISO?6469?3. |
In IEC 61557-8 and GB/T 18487.1, the warning (500Ω / V d.c. – 2mA) and fault (100Ω / V d.c. – 10mA) thresholds are set for the resistance of the isolation barrier. The IMD circuit monitors the insulation resistance and reports a failure in the case of insufficient insulation resistance. In the event of insufficient insulation resistance, current leakage can potentially increase above the permissible limit.
Figure 1-1 illustrates that an insulation monitoring device (IMD) is installed on both the charger side and the vehicle side. The two IMDs cooperate to supervise the isolation barrier of the DC power?supply circuit throughout the entire charging process and while the vehicle is in operation.
According to GB/T?18487.1?2023, the following sequence and requirements apply:
Therefore, these two IMD circuits work together to verify that the insulation resistance remains within the normal range during charging and driving, in both the charging end and vehicle end.
Whether AC is charging or DC is fast charging, there is generally a residual current detection (RCD) circuit on the AC side in both cases. There is a slight difference between the functions of the RCD and IMD circuits. The RCD circuit determines the insulation failure by monitoring the total leakage current, whereas, the IMD circuit monitors the insulation resistance. Table 1-2 presents a comparison between the IMD and RCD circuits.
| Method | RCD | IMD |
|---|---|---|
| Purpose | Detects an imbalance between phase and neutral, which indicates a fault?to?earth path and quickly disconnects the supply. | Verifies that the isolation barrier (HV?± to protective earth) remains above a prescribed resistance value. |
| Principle | Measures the sum of currents in the conductors. Any residual
current larger than the set threshold trips the device. Rated current < 30mA DC current < 6mA |
Measures the insulation resistance by injecting a test voltage
through a high?ohmic path and reading the resulting current. Safe: > 500Ω / V Warning: ?100Ω / V to 500Ω / V Fault: < 100Ω / V. |
| Locations | Typically installed upstream of the user?accessible load on the
AC side. For DC fast?charging stations: An RCD can be placed on the DC link as an extra protection device. |
|
| Response Time | ≤30ms (typical) for 30mA devices. | ≤10s (IEC?61557?8) for fault detection; many OEMs require ≤5s. Continuous monitoring at 0.5–1s interval is common. |
| Operation Mode | Instantaneous trip on the detection of residual current; does not perform a precharge insulation check. | Continuous monitoring of insulation resistance before and during power flow. Precharge verification is mandatory. |
| Options | Current transformer. | Electric bridge switch. |
| Reference Design | TIDA-010237 | TIDA-010232 (DC side), TIDA-020085 (AC side) |
The existing IMD and RCD circuits cover scenarios for unidirectional OBCs. However, with the emergence of bidirectional power flow capabilities in electric vehicle (EV) onboard chargers (OBCs), these systems not only enable traditional grid-to-vehicle charging but also reverse power flow in the applications. Enhanced safety measures are critical for protecting users from potential electrical shock hazards from insulation failures, as EVs increasingly function as mobile power sources. Therefore, new requirements on insulation monitoring exists: